Power Systems A gas turbine power plant is best suited for Peak load. Emergency. None of these. Base load. Peak load. Emergency. None of these. Base load. ANSWER DOWNLOAD EXAMIANS APP
Power Systems The positive, negative and zero sequence per unit impedance of two generators connected in parallel are X1 = 0.12 pu, X2 = 0.096 pu and X0 = 0.036 pu. For LG fault at generator terminals (with 1 pu voltage) the positive sequence current will be 9.936 pu 8.936 pu 10.936 pu 7.936 pu 9.936 pu 8.936 pu 10.936 pu 7.936 pu ANSWER DOWNLOAD EXAMIANS APP
Power Systems In a 400 kV power network, 360 kV is recorded at 400 kV bus. The reactive power absorbed by a shunt reactor for 50 MVAr, 400 kV connected at the bus is 45.0 MVAr. 40.5 MVAr. 55.56 MVAr. 61.73 MVAr. 45.0 MVAr. 40.5 MVAr. 55.56 MVAr. 61.73 MVAr. ANSWER DOWNLOAD EXAMIANS APP
Power Systems The steam power plant efficiency can be improved by decreasing the load on the plant. burning large amount of coal. using high temperature and high pressure steam. using large quantity of water. decreasing the load on the plant. burning large amount of coal. using high temperature and high pressure steam. using large quantity of water. ANSWER DOWNLOAD EXAMIANS APP
Power Systems Which of the following method is used for changing power factor from leading to lagging any of the above shunt capacitor shunt reactor series capacitor any of the above shunt capacitor shunt reactor series capacitor ANSWER DOWNLOAD EXAMIANS APP
Power Systems For complete protection of 3-phase system from the short circuit faults minimum number of relays required are one six three two one six three two ANSWER DOWNLOAD EXAMIANS APP