A 1000 kVA ONAN cooled transformer has a load of 500 kVA throughout the day except for a period of 2 hours. What is the permissible overload for a duration of two hours. Assume the permissible load kVA as a fraction of rated kVA is 1.43.

715 kVA
700 kVA
1430 kVA
1050 kVA

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 3)
In transformers,
Statement 1: Deterioration of oil may occur due to the result of prolonged overloading of the transformer.
Statement 2: Dielectric faults occur in the winding due to turn-to-turn insulation breakdown.

Statement 1 is FALSE and Statement 2 is TRUE
Both Statement 1 and Statement 2 are TRUE
Statement 1 is TRUE and Statement 2 is FALSE
Both Statement 1 and Statement 2 are FALSE

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 3)
Determine the ohmic value of the current limiting reactor per phase external to a 40 MVA, 15 kV, 50 Hz, three phase synchronous generator which can limit the current on short circuit of 6 times the full load current. The reactance of the synchronous generator is 0.06 pu.

0.6 Ω
0.2 Ω
0.4 Ω
0.8 Ω

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 3)
The DC offset in fault current causes conventional over-current (OC) relays to :

sometimes under-reach and sometimes over-reach
reach remains unaffected due to DC offset
over-reach
under-reach