A 1000 kVA ONAN cooled transformer has a load of 500 kVA throughout the day except for a period of 2 hours. What is the permissible overload for a duration of two hours. Assume the permissible load kVA as a fraction of rated kVA is 1.43.

700 kVA
1050 kVA
715 kVA
1430 kVA