A 1000 kVA ONAN cooled transformer has a load of 500 kVA throughout the day except for a period of 2 hours. What is the permissible overload for a duration of two hours. Assume the permissible load kVA as a fraction of rated kVA is 1.43.

715 kVA
1050 kVA
700 kVA
1430 kVA

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 3)
હું અહી આવી શકું' વાક્યને સ્થળવાચક ક્રીયાવીશેષણમાં ફેરવો.

હું આજે નહિ આવી શકું.
હું નિયમિત રીતે અહી આવી શકું.
હું ચેન્નાઈ નહિ આવી શકું.
હું કદી પણ નહિ આવી શકું.

ANSWER DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 3)
The most commonly used method for the protection of three phase feeder is

Reverse power protection
Differential protection
None of these
Time graded protection

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP