Power Systems The voltage and current instantaneous values are given as 5 sin (ωt + 30°) pu and 2 sin (ωt - 15°) pu respectively. Find the per unit active power? 5.353 pu 7 pu 3.535 pu 5 pu 5.353 pu 7 pu 3.535 pu 5 pu ANSWER DOWNLOAD EXAMIANS APP
Power Systems Which of the following is not a secondary nuclear fuel None of above. Pu239. U233. U235. None of above. Pu239. U233. U235. ANSWER DOWNLOAD EXAMIANS APP
Power Systems The pickup value of relay is 6.5 Amp and fault current in relay coil is 39 Amp. Its plug setting multiplier is 10 A. 7 A. 6 A. 8 A. 10 A. 7 A. 6 A. 8 A. ANSWER DOWNLOAD EXAMIANS APP
Power Systems A generated station has a maximum demand of 30 MW, a load factor of 60% and a plant capacity factor of 50%. The reserve capacity of the plant is 5 MW 10 MW 12 MW 6 MW 5 MW 10 MW 12 MW 6 MW ANSWER DOWNLOAD EXAMIANS APP
Power Systems A power station plant load factor is defined as the ratio of average load to the peak load minimum load to peak load minimum load to average load the energy generated to that of maximum energy that could have been generated average load to the peak load minimum load to peak load minimum load to average load the energy generated to that of maximum energy that could have been generated ANSWER DOWNLOAD EXAMIANS APP
Power Systems A 3-phase transmission line operating at Vs = 400 kV and has ABCD parameters A= D = 0.8∠0°, B = 100∠°90 Ω, C = 0.5*10^-6∠90° ℧. Find Charging current under no load? 0.144∠90° A/phase 1.144∠90° A/phase 0.344∠90° A/phase 0.512∠90° A/phase 0.144∠90° A/phase 1.144∠90° A/phase 0.344∠90° A/phase 0.512∠90° A/phase ANSWER DOWNLOAD EXAMIANS APP