Power Systems The pickup value of relay is 6.5 Amp and fault current in relay coil is 39 Amp. Its plug setting multiplier is 10 A. 6 A. 7 A. 8 A. 10 A. 6 A. 7 A. 8 A. ANSWER DOWNLOAD EXAMIANS APP
Power Systems If the fault current is 2000 A, the relay setting is 50% and CT ratio is 400 : 5, then plug setting multiplier will be 25. 10. 15. 50. 25. 10. 15. 50. ANSWER DOWNLOAD EXAMIANS APP
Power Systems The Gauss Seidel load flow method has following disadvantages. Which of the following statement is wrong? Slow convergence A good initial guess for voltages is essential for convergence Unreliable convergence Choice of slack bus affects the convergence Slow convergence A good initial guess for voltages is essential for convergence Unreliable convergence Choice of slack bus affects the convergence ANSWER DOWNLOAD EXAMIANS APP
Power Systems Find the characteristic impedance of a transmission line, if impedance is 16 Ω and admittance is 0.1 mâ„§? 200 Ω 160 Ω 400 Ω 320 Ω 200 Ω 160 Ω 400 Ω 320 Ω ANSWER DOWNLOAD EXAMIANS APP
Power Systems Find the number of strands of ACSR conductor for 3 layer transmission line? 19 29 7 1 19 29 7 1 ANSWER DOWNLOAD EXAMIANS APP
Power Systems Peterson coil is used in case of transmission line for compensation of arcing grounds increase the voltage level improve power factor reduce ferranti effect compensation of arcing grounds increase the voltage level improve power factor reduce ferranti effect ANSWER DOWNLOAD EXAMIANS APP