Power Systems Generation of of one watt needs about ______________ fission per second 3.1. 3.1 × 107. 3.1 × 1010. 3.1 × 106. 3.1. 3.1 × 107. 3.1 × 1010. 3.1 × 106. ANSWER DOWNLOAD EXAMIANS APP
Power Systems A generated station has a maximum demand of 30 MW, a load factor of 60% and a plant capacity factor of 50%. The reserve capacity of the plant is 5 MW 10 MW 6 MW 12 MW 5 MW 10 MW 6 MW 12 MW ANSWER DOWNLOAD EXAMIANS APP
Power Systems The water from a catchment is 60*106 cu m annually and hydro station has head of 40 m. Assuming ideal generator and turbine, the power that can be theoretically generated is 750 kW 250 kW 500 kW 300 kW 750 kW 250 kW 500 kW 300 kW ANSWER DOWNLOAD EXAMIANS APP
Power Systems For variable heads of near about but less than 30 m, which type of turbines is used hydro power plant Francis. None of above. Pelton. Kaplan. Francis. None of above. Pelton. Kaplan. ANSWER DOWNLOAD EXAMIANS APP
Power Systems In a biased differential relay the bias is defined as the ratio of number of turns of restraining and operating coil. operating coil current and restraining coil current. fault current and restraining coil current. fault current and operating coil current. number of turns of restraining and operating coil. operating coil current and restraining coil current. fault current and restraining coil current. fault current and operating coil current. ANSWER DOWNLOAD EXAMIANS APP
Power Systems If in a line, resistance and reactance are found to be equal and regulation is zero, then load will have 0.707 leading power factor zero power factor unity power factor 0.707 lagging power factor 0.707 leading power factor zero power factor unity power factor 0.707 lagging power factor ANSWER DOWNLOAD EXAMIANS APP