DGVCL Exam Paper (11-12-2011) If the percentage reactance of the system upto the point of fault is 20% and the base kVA is 10,000 the short ciruit kVA is 60 MVA 10 MVA 20 MVA 50 MVA 60 MVA 10 MVA 20 MVA 50 MVA ANSWER EXPLANATION DOWNLOAD EXAMIANS APP Short circuit kVA = Base kVA/%X
DGVCL Exam Paper (11-12-2011) If the fault current is 2000 A, the relay plug setting is 50% and the CT ratio is 400/5, the plug setting multiple will be 10 25 15 50 10 25 15 50 ANSWER DOWNLOAD EXAMIANS APP
DGVCL Exam Paper (11-12-2011) Which lightning stroke is most dangerous? Direct stroke on ground wire Direct stoke on tower top Direct stroke on line conductor Indirect stroke on conductor Direct stroke on ground wire Direct stoke on tower top Direct stroke on line conductor Indirect stroke on conductor ANSWER DOWNLOAD EXAMIANS APP
DGVCL Exam Paper (11-12-2011) A device connected to the computer which converts digital signals to analog and vice-versa is CPU Keyboard UPS Modem CPU Keyboard UPS Modem ANSWER DOWNLOAD EXAMIANS APP
DGVCL Exam Paper (11-12-2011) In a power plant, a reserve generating capacity which is not in service but is in operation is known as Hot reserve Spinning reserve Firm power Cold reserve Hot reserve Spinning reserve Firm power Cold reserve ANSWER DOWNLOAD EXAMIANS APP
DGVCL Exam Paper (11-12-2011) If the excitation of a synchronous generator fails, it acts as a Induction motor Synchronous generator Synchronous motor Induction generator Induction motor Synchronous generator Synchronous motor Induction generator ANSWER EXPLANATION DOWNLOAD EXAMIANS APP if excitation of synchronous generator fails, operate as induction motor