Power Systems If the percentage reactance of an element is 20 % and the full load current is 50 Amp, the short circuit current will be 350 Amp. 200 Amp. 300 Amp. 250 Amp. 350 Amp. 200 Amp. 300 Amp. 250 Amp. ANSWER DOWNLOAD EXAMIANS APP
Power Systems When reactance grounding is used in network, the voltage between neutral and ground is both 1 and 3 3×IR0 × Xn IR0 × Xn IN × Xn both 1 and 3 3×IR0 × Xn IR0 × Xn IN × Xn ANSWER DOWNLOAD EXAMIANS APP
Power Systems A pin type insulator has 100 kV puncture voltage. If 10 kV flash over voltage occurred in a transmission line, then find the safety factor of insulator? 0.1 1000 10 0.001 0.1 1000 10 0.001 ANSWER DOWNLOAD EXAMIANS APP
Power Systems In a 3-phase, 5 kV, 5 MVA system, what is the base impedance? 500 ohms 50 ohms 0.5 ohm 5 ohms 500 ohms 50 ohms 0.5 ohm 5 ohms ANSWER DOWNLOAD EXAMIANS APP
Power Systems An ACSR conductor has a diameter of 2 cm has internal inductance of 0.05 mH/Km. If this ACSR is replaced with another having a diameter of 4 cm then its internal inductance is 0.025 mH/Km 0.05 mH/Km 0.1 mH/Km 0 mH/Km 0.025 mH/Km 0.05 mH/Km 0.1 mH/Km 0 mH/Km ANSWER DOWNLOAD EXAMIANS APP
Power Systems A transmission line has self and mutual impedances of 0.8 pu and 0.2 pu. Find the positive, negative and zero sequence impedances respectively? 0.6, 0.6 and 1.2 pu 0.6, 0.8 and 1.2 pu 0.8, 0.8 and 1.2 pu 0.8, 0.6 and 1.2 pu 0.6, 0.6 and 1.2 pu 0.6, 0.8 and 1.2 pu 0.8, 0.8 and 1.2 pu 0.8, 0.6 and 1.2 pu ANSWER DOWNLOAD EXAMIANS APP