Power Systems If the percentage reactance of an element is 20 % and the full load current is 50 Amp, the short circuit current will be 350 Amp. 250 Amp. 300 Amp. 200 Amp. 350 Amp. 250 Amp. 300 Amp. 200 Amp. ANSWER DOWNLOAD EXAMIANS APP
Power Systems The load duration curve for a system is 8 hours 30 MW, 16 hours 25 MW and 24 hours 20 MW. The load factor will be 0.83. 0.25. 1.3. 0.44. 0.83. 0.25. 1.3. 0.44. ANSWER DOWNLOAD EXAMIANS APP
Power Systems If the fault current is 2000 A, the relay setting is 50% and CT ratio is 400 : 5, then plug setting multiplier will be 25. 15. 50. 10. 25. 15. 50. 10. ANSWER DOWNLOAD EXAMIANS APP
Power Systems Critical mass of the fuel is the amount required to make the multiplication factor more than 1. equal to factor. 0.5. less than 1. more than 1. equal to factor. 0.5. less than 1. ANSWER DOWNLOAD EXAMIANS APP
Power Systems The arc voltage produced in an AC circuit breaker is always in phase with the arc current. lagging the arc current by 90°. leading the arc current by 90°. in phase opposition with the arc current. in phase with the arc current. lagging the arc current by 90°. leading the arc current by 90°. in phase opposition with the arc current. ANSWER DOWNLOAD EXAMIANS APP
Power Systems Four identical alternators each are rated for 20 MVA, 11 KV having a subtransient reactance of 16% are working in parallel. The short circuit level at the busbar is 100 MVA 400 MVA 500 MVA 125 MVA 100 MVA 400 MVA 500 MVA 125 MVA ANSWER DOWNLOAD EXAMIANS APP