MGVCL Exam Paper (30-07-2021 Shift 3)
Consider a solar PV plant with the following specific conditions:
Analysis period: 1 year
Measured average solar irradiation intensity in 1 year: 150 kWh/m²
Generator area of the PV plant: 10 m² Efficiency factor of the PV modules: 15%
Electrical energy actually exported by plant to grid: 135 kWh
Calculate the performance ratio.

80%
60%
75%
50%

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 3)
The DC offset in fault current causes conventional over-current (OC) relays to :

sometimes under-reach and sometimes over-reach
reach remains unaffected due to DC offset
under-reach
over-reach

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 3)
In transformers,
Statement 1: Deterioration of oil may occur due to the result of prolonged overloading of the transformer.
Statement 2: Dielectric faults occur in the winding due to turn-to-turn insulation breakdown.

Statement 1 is TRUE and Statement 2 is FALSE
Both Statement 1 and Statement 2 are TRUE
Both Statement 1 and Statement 2 are FALSE
Statement 1 is FALSE and Statement 2 is TRUE

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 3)
In a single phase energy meter, the pressure / voltage coil is wound on

both the limbs of the laminated core with same turns
the edges of the limb on the laminated core
the centre limb of the laminated core / the middle limb of the shunt magnet
both the limbs of the laminated core with different turns

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP