Power Systems Based on the discharge, Kaplan turbine will discharge 1000 lpm >10000 lpm 1000 lpm >10000 lpm ANSWER DOWNLOAD EXAMIANS APP
Power Systems The thermal efficiency of BWR is equal to that of PWR. greater than that of PWR. less than that of PWR. None of these equal to that of PWR. greater than that of PWR. less than that of PWR. None of these ANSWER DOWNLOAD EXAMIANS APP
Power Systems The positive, negative and zero sequence per unit impedance of two generators connected in parallel are X1 = 0.12 pu, X2 = 0.096 pu and X0 = 0.036 pu. For LG fault at generator terminals (with 1 pu voltage) the positive sequence current will be 10.936 pu 7.936 pu 9.936 pu 8.936 pu 10.936 pu 7.936 pu 9.936 pu 8.936 pu ANSWER DOWNLOAD EXAMIANS APP
Power Systems A power station supplies the peak load of 50 MW, 40 MW and 70 MW to three localities. The annual load factor is 0.50 p.u. and the diversity factor of the load at the station is 1.55 the maximum demand on the station and average load respectively will be 57.5 MW. 53 MW. 52 MW. 51.61 MW. 57.5 MW. 53 MW. 52 MW. 51.61 MW. ANSWER DOWNLOAD EXAMIANS APP
Power Systems Reactance relays are used for the protection of All of these medium transmission lines only long transmission lines only short transmission lines only All of these medium transmission lines only long transmission lines only short transmission lines only ANSWER DOWNLOAD EXAMIANS APP
Power Systems Surge impedance loading of a 3-phase, 400 kV transmission line is 400 Ω. The surge impedance loading is 800 MW 1600 MW 400 MW 200 MW 800 MW 1600 MW 400 MW 200 MW ANSWER DOWNLOAD EXAMIANS APP