MGVCL Exam Paper (30-07-2021 Shift 2)
A 50 Hz synchronous generator is connected to an infinite bus through a line. The p.u. reactances of generator and the line are j0.3 p.u. and j0.2 p.u. respectively. The generator no load voltage is 1.1 p.u. and that of infinite bus is 1.0 p.u. The inertia constant of the generator is 4 MW-sec/MVA. Determine the frequency of natural oscillations if the generator is loaded to 60% of its maximum power transfer capacity and small perturbation in power is given.

1.62 Hz
1.32 Hz
1.52 Hz
1.42 Hz

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
A generating station having 'n' section busbars each rated at Q kVA with ×% reactance is connected on the tie-bars systems through busbar reactances of b%. Determine the short circuit kVA if a 3-phase fault takes place on one section.

Q[(1/x) + (n+1)/(bn+x)]
Q[(1/x) + (n+1)/(bn-x)]
Q[(1/x) - (n+1)/(bn-x)]
Q[(1/x) + (n-1)/(bn+x)]

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
In a single phase energy meter, the shunt electromagnet is energized by a ____of ____

pressure coil, thin wire of more turns
current coil, thick wire of few turns
pressure coil, thick wire of few turns
current coil, thin wire of more turns

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
A 3-phase motor load has a p.f. of 0.397 lagging. The two wattmeter method used to measure power show the input as 30 kW. Find the reading on each wattmeter.

W1 = -5 kW and W2 = 35 kW
W1 = 5 kW and W2 = 25 kW
W1 = -10 kW and W2 = 40 kW
W1 = 10 kW and W2 = 20 kW

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
Interposing current-transformer (CT) is used in differential protection of a transformer to

limit the main CT secondary current
increase the sensitivity of the relay
minimize the effect of saturation of the main CTs
match the standard ratio of CTs used on both sides of the transformer winding

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP