Power Systems
A 1- phase transmission line operating at 30 kV has radius of 1 cm and distance between conductors is 0.5 m. Assume m = δ =1, g = 21 kV/cm and frequency f = 50 Hz. Find the critical disruptive voltage?

 82.15 kV/phase
 34.64 kV/phase
 17.32 kV/phase
 41.075 kV/phase

ANSWER DOWNLOAD EXAMIANS APP

Power Systems
In coal fired thermal power stations, what are the electrostatic precipitators used for?

All of these
 To remove dust particles setting on the bus bar conductors in the station switch yard
 To keep the air heaters clean
 To collect the dust particles from the flue gases

ANSWER DOWNLOAD EXAMIANS APP