Electrical Machines
The result of slip test on a 3-phase, 20 KVA, 400 V, 50 Hz connected salient pole alternator is given below- Phase value: Vmax = 100 V, Vmin = 96 V, Imax = 10 A and I min = 7 A. The direct and quadranature axis reactances are respectively

 8.248 and 9.60 Ω.
 8.248 and 5.54 Ω.
 14.28 and 9.60 Ω.
  14.28 and 5.54 Ω.

ANSWER DOWNLOAD EXAMIANS APP

Electrical Machines
In an alternator, voltage drops occurs in

  armature resistance, leakage reactance, armature reaction and earth connection.
  armature resistance and leakage reactance.
  armature resistance, leakage reactance and armature reaction.
  armature resistance only.

ANSWER DOWNLOAD EXAMIANS APP