Electrical Machines
The result of slip test on a 3-phase, 20 KVA, 400 V, 50 Hz connected salient pole alternator is given below- Phase value: Vmax = 100 V, Vmin = 96 V, Imax = 10 A and I min = 7 A. The direct and quadranature axis reactances are respectively

 8.248 and 5.54 Ω.
 8.248 and 9.60 Ω.
 14.28 and 9.60 Ω.
  14.28 and 5.54 Ω.

ANSWER DOWNLOAD EXAMIANS APP

Electrical Machines
A DC shunt generator builds up to a voltage of 220 V at no load while running at its rated speed. If the speed of the generator is raised by 25% kepping the circuit conditions unaltered, then the Voltage to which the machine would build up will

 increase to 1.25 times 220 V
 not change and remain at 220 V
 increase to value lying between 220 V and 1.25 times 220 V
 increase to a value greater than 1.25 times 220 V

ANSWER DOWNLOAD EXAMIANS APP

Electrical Machines
The results of a slip test for determining direct axis (Xd) and quadrature axis (Xq) reactances of a star connected salient pole alternator are given below Phase values: Vmax = 108 V ; Vmin = 96 V Imax = 12 A ; Imin = 10 A Hence the two reactances will be

 Xd = 10.8Ω and Xq = 8Ω
 Xd = 8Ω and Xq = 10.8Ω
 Xd = 9.6Ω and Xq = 9Ω
 Xd = 9Ω and Xq = 9.6Ω

ANSWER DOWNLOAD EXAMIANS APP