Power Systems The inertia constant of 100 MVA, 50 Hz, 4 pole generator is 10 MJ/MVA. If the mechanical input to the machine is suddenly raised from 50 MW to 75 MW, the rotor acceleration will be equal to 12.5 electrical degrees/s² 125 electrical degrees/s² 22.5 electrical degrees/s² 225 electrical degrees/s² 12.5 electrical degrees/s² 125 electrical degrees/s² 22.5 electrical degrees/s² 225 electrical degrees/s² ANSWER DOWNLOAD EXAMIANS APP
Power Systems Which of the following effects are associated with transmission line ferranti effect All of these corona effect skin effect ferranti effect All of these corona effect skin effect ANSWER DOWNLOAD EXAMIANS APP
Power Systems Positive, negative and zero sequence impedances of line are 2,2 and 5 pu respectively. Find self and mutual impedances respectively? 2 and 2 pu 3 and 1 pu 2 and 5 pu 1 and 3 pu 2 and 2 pu 3 and 1 pu 2 and 5 pu 1 and 3 pu ANSWER DOWNLOAD EXAMIANS APP
Power Systems The insulation resistance of the 20 km long underground cable is 8 MΩ. Other things being same, the insulation resistance of 10 km long cable will be 32 MΩ 16 MΩ 4 MΩ 8 MΩ 32 MΩ 16 MΩ 4 MΩ 8 MΩ ANSWER DOWNLOAD EXAMIANS APP
Power Systems For n bus power system size of Y bus matrix is (n-2)×(n-2) (n-1)×(n-1) (n-1)×(n-2) n×n (n-2)×(n-2) (n-1)×(n-1) (n-1)×(n-2) n×n ANSWER DOWNLOAD EXAMIANS APP
Power Systems Maximum efficiency of modern coal fired steam raising thermal power plants is restricted to about 035 (a low value), mainly because of low alternative efficiency. high energy loss in boiler. high energy loss from turbine exhaust to condenser. low steam turbine mechanical efficiency. low alternative efficiency. high energy loss in boiler. high energy loss from turbine exhaust to condenser. low steam turbine mechanical efficiency. ANSWER DOWNLOAD EXAMIANS APP