Electrical Machines
The DC generator runs at a speed of 1000 rpm and flux per pole is 0.2 Wb, number of poles are 2 the winding is wave wound and having 480 conductors. The critical speed is 1200 rpm. Then the generated emf ( Eg )

 2000 Volt.
  0 Volt.
 1500 Volt.
 1600 Volt.

ANSWER DOWNLOAD EXAMIANS APP

Electrical Machines
The result of slip test on a 3-phase, 20 KVA, 400 V, 50 Hz connected salient pole alternator is given below- Phase value: Vmax = 100 V, Vmin = 96 V, Imax = 10 A and I min = 7 A. The direct and quadranature axis reactances are respectively

 14.28 and 9.60 Ω.
 8.248 and 5.54 Ω.
  14.28 and 5.54 Ω.
 8.248 and 9.60 Ω.

ANSWER DOWNLOAD EXAMIANS APP