Electrical Machines
Ratio of starting torque to full load torque is minimum in

  Series motor.
  Differential compound motor.
  Cumulative compound motor.
  Shunt motor.

ANSWER DOWNLOAD EXAMIANS APP

Electrical Machines
The result of slip test on a 3-phase, 20 KVA, 400 V, 50 Hz connected salient pole alternator is given below- Phase value: Vmax = 100 V, Vmin = 96 V, Imax = 10 A and I min = 7 A. The direct and quadranature axis reactances are respectively

 14.28 and 9.60 Ω.
 8.248 and 5.54 Ω.
  14.28 and 5.54 Ω.
 8.248 and 9.60 Ω.

ANSWER DOWNLOAD EXAMIANS APP

Electrical Machines
Two synchronous generators operating in parallel 200 MW and 400 MW respectively. The drooping characteristics of their governors are 4% and 5% from no load to full load. Consider the governors operating at 50Hz on no load. How will the machine share, if the load is 600 MW?

 generator 1 gets over load
None of these
 200 MW and 400MW
 generator 2 gets over load

ANSWER DOWNLOAD EXAMIANS APP