No of disc required for 11 kV transmission line = 1 disc Since the transmission line is 3-phase, therefore, the number of discs required for a single-pole will be 3. Total no. of poles = 80 No of disc = 3 × 80 = 240
The factor by which, the induced E.M.F gets reduced due to short pitching is called pitch factor or coil span factor denoted by Kc. It is given as Kc = cosα/2 given α = 60° Kc = cos60/2 Kc = cos30° Kc = √3/2
Indian Electricity Rules specify that the maximum load on a power sub-circuit should not exceed 3000 watts and the number of outlets should be limited to two.
A phase sequence is an order or sequence in which the currents or voltages of different phases attain their maximum values. In a three-phase system, there are only two possible phase sequences: R-Y-B (positive Phase Sequence) and R-B-Y (Negative Phase Sequence).