Switch Gear Which of the following CB's is generally used in railways applications ? air break circuit breaker low oil circuit breaker sf 6 circuit breaker bulk oil circuit breaker air break circuit breaker low oil circuit breaker sf 6 circuit breaker bulk oil circuit breaker ANSWER DOWNLOAD EXAMIANS APP
Switch Gear HRC fuses provide best protection against reverse current overload short circuits open circuits reverse current overload short circuits open circuits ANSWER DOWNLOAD EXAMIANS APP
Switch Gear Air blast circuit breakers for 400 kV power system are designed to operate in 0.1 sec 100 micro-second 0.5 sec 50 milli-second 0.1 sec 100 micro-second 0.5 sec 50 milli-second ANSWER DOWNLOAD EXAMIANS APP
Switch Gear A three phase circuit breaker is rated at 2000 MVA, 33 kv. The symmetrical breaking current is 80 kA 60 kA 35 kA 20 kA 80 kA 60 kA 35 kA 20 kA ANSWER DOWNLOAD EXAMIANS APP
Switch Gear The pick-up current of a relay is 7.5 A and the fault current in relay is 30 A. Its plug-setting multiplier (P.S.M.) is 4 2 6 8 4 2 6 8 ANSWER DOWNLOAD EXAMIANS APP
Switch Gear The voltage appearing across the contacts after opening of the circuit breaker is called surge voltage recovery voltage arc voltage operating voltage surge voltage recovery voltage arc voltage operating voltage ANSWER DOWNLOAD EXAMIANS APP