Power Systems The power generated by two plants are; P1 = 50 MW, P2 = 40 MW. If the loss coefficients are B11 = 0.001, B22 = 0.0025 and B12 = -0.0005, then power loss will be 8.5 MW 4.5 MW 5.5 MW 6.5 MW 8.5 MW 4.5 MW 5.5 MW 6.5 MW ANSWER DOWNLOAD EXAMIANS APP
Power Systems A transmission line has a surge impedance of 400 Ω for a length of the line of 200 km. If the length of line is increased to 400 km, then its surge impedance is 800 Ω 0 Ω 200 Ω 400 Ω 800 Ω 0 Ω 200 Ω 400 Ω ANSWER DOWNLOAD EXAMIANS APP
Power Systems If, for a given alternator in economic operation mode, the incremental cost is given by (0.012 P + 8) Rs/MWh, dPL/dP = 0.2 and plant λ = 25, then power generation is 1500 MW 1250 MW 1000 MW 750 MW 1500 MW 1250 MW 1000 MW 750 MW ANSWER DOWNLOAD EXAMIANS APP
Power Systems A transmission line has a surge impedance of 400 Ω is connected with the cable having surge impedance of 40 Ω, a surge magnitude of 100 kV is travelling from the transmission line towards the cable. Find the transmitted voltage? 100 kV 18.18 kV 36. 36 kV 30.6 Kv 100 kV 18.18 kV 36. 36 kV 30.6 Kv ANSWER DOWNLOAD EXAMIANS APP
Power Systems An over current relay, having a current setting of 125% connected to a supply circuit through a current transformer of ratio 500/5. The plug setting multiplier for a fault current of 5 kA is 6 2 8 5 6 2 8 5 ANSWER DOWNLOAD EXAMIANS APP
Power Systems In a 400 kV power network, 360 kV is recorded at 400 kV bus. The reactive power absorbed by a shunt reactor for 50 MVAr, 400 kV connected at the bus is 55.56 MVAr. 40.5 MVAr. 45.0 MVAr. 61.73 MVAr. 55.56 MVAr. 40.5 MVAr. 45.0 MVAr. 61.73 MVAr. ANSWER DOWNLOAD EXAMIANS APP