Power Systems The charging current of a 400 kV line is more than that of a 220 kV line of the same length? None of these False either 1 or 2 True None of these False either 1 or 2 True ANSWER DOWNLOAD EXAMIANS APP
Power Systems The ground capacitance existing between transmission line and ground is 4µF. Find the inductive reactance of the peterson coil for compensation of arcing grounds? 625.35 Ω 265.25 Ω 855.26 Ω 0.844 Ω 625.35 Ω 265.25 Ω 855.26 Ω 0.844 Ω ANSWER DOWNLOAD EXAMIANS APP
Power Systems A loss less transmission line having surge impedance loading (SIL) of 2280 MW is provided with a uniformly distributed series capacitive compensation of 30 %. Then SIL of compensated transmission line will be 2280 MW. 3257 MW. 1835 MW. 2725 MW. 2280 MW. 3257 MW. 1835 MW. 2725 MW. ANSWER DOWNLOAD EXAMIANS APP
Power Systems In a 400 kV power network, 360 kV is recorded at 400 kV bus. The reactive power absorbed by a shunt reactor for 50 MVAr, 400 kV connected at the bus is 40.5 MVAr. 61.73 MVAr. 45.0 MVAr. 55.56 MVAr. 40.5 MVAr. 61.73 MVAr. 45.0 MVAr. 55.56 MVAr. ANSWER DOWNLOAD EXAMIANS APP
Power Systems In a 3-phase, 5 kV, 5 MVA system, what is the base impedance? 500 ohms 0.5 ohm 50 ohms 5 ohms 500 ohms 0.5 ohm 50 ohms 5 ohms ANSWER DOWNLOAD EXAMIANS APP