Economics of Power Generation The correct relation in the following is : kVAR = kW cos Ф Not listed here kVAR = kW tan Ф kVAR = kW Sin Ф kVAR = kW cos Ф Not listed here kVAR = kW tan Ф kVAR = kW Sin Ф ANSWER DOWNLOAD EXAMIANS APP
Economics of Power Generation Improving the power factor means making it None of the listed here Zero Close to unity Less than 0.5 None of the listed here Zero Close to unity Less than 0.5 ANSWER DOWNLOAD EXAMIANS APP
Economics of Power Generation When the power factor is improved, the lagging kVAR drawn from the supply will Increase Decreases None of the listed here Remains same Increase Decreases None of the listed here Remains same ANSWER DOWNLOAD EXAMIANS APP
Articles Egg are sold by ___ dozen. The A No article An The A No article An ANSWER DOWNLOAD EXAMIANS APP
Economics of Power Generation A load draws a power of 10 kW at a power factor of 0.707 lagging. The lagging kVAR drawn from the supply will be 10 kVAR 5 kVAR 15kVAR 20 kVAR 10 kVAR 5 kVAR 15kVAR 20 kVAR ANSWER DOWNLOAD EXAMIANS APP