Determine the ohmic value of the current limiting reactor per phase external to a 30 MVA, 11 kV, 50 Hz, three phase synchronous generator which can limit the current on short circuit of 5 times the full load current. The reactance of the synchronous generator is 0.05 pu.

0.305 Ω
0.405 Ω
0.605 Ω
0.805 Ω

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 1)
A balanced delta connected load of 8+j6 Ω per phase is connected to a 415 V, 50 Hz, 3-phase supply lines. If the input power factor is improved to 0.9 by connecting a star connected capacitor bank, then the required kVAR of the bank is

8.98 kVAR
16.98 kVAR
14.98 kVAR
10.98 kVAR