Determine the ohmic value of the current limiting reactor per phase external to a 30 MVA, 11 kV, 50 Hz, three phase synchronous generator which can limit the current on short circuit of 5 times the full load current. The reactance of the synchronous generator is 0.05 pu.
The ratio of full load current to short circuit current = 1/5 Xsc = j/(1/5) External reactance required = j*((1/5) - 0.05)) = j*0.15 pu Full load current = (30*1000)/(√3*11) = 1574.6 A Per unit reactance = j*0.15 = (I*Xr)/V j*0.15 = (1574.6*Xb)/((11/√3)*1000)) = 0.60 ohm
The V-curves of a synchronous motor show relationship between Armature current (Ia) and Excitation current (If). The Inverted V-curves of a synchronous motor show relationship between power factor (pf) and field excitation (If).
As per the key statistics data of IEA With electricity consumption reached to 1,164 TWh in the country till November 2019, India ranked third among the top ten electricity consuming countries across the globe.
Two-part tariff: In this type of tariff, the total bill is divided into two parts. The first one is the fixed charge and the second is the running charge. The fixed charge is because of the maximum demand and the second charge depends on the energy consumption by the load.