MGVCL Exam Paper (30-07-2021 Shift 1)
Determine the ohmic value of the current limiting reactor per phase external to a 30 MVA, 11 kV, 50 Hz, three phase synchronous generator which can limit the current on short circuit of 5 times the full load current. The reactance of the synchronous generator is 0.05 pu.

0.405 Ω
0.305 Ω
0.805 Ω
0.605 Ω

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 1)
The expression for voltage regulation of a short transmission line for lagging power factor is given by: ___, where, 'I' is the line current, 'V_r' is the receiving end voltage, 'R' is the line resistance and 'X' is the line reactance.

(IR cosφ_r + IX sinφ_r)/V_r
(IX cosφ_r + IR sinφ_r)/V_r
(IR cosφ_r - IX sinφ_r)/V_r
(IX cosφ_r - IR sinφ_r)/V_r

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 1)
Determine maximum permissible load which a 15 MVA, ONAN cooled transformer to IS : 2026 can take for 6 hr, if the initial load on it was 12 MVA. The weighted ambient temperature is 20˚C. Assume the permissible load kVA as a fraction of rated kVA is 1.25.

12 MVA
15 MVA
9.6 MVA
18.75 MVA