Power Systems
A transmission line is operating under no load has ABCD parameters B = 100∠90° has a phase shift of 0.2 rad, how much shunt reactor is required for compensation of ferranti effect?

 15.9 H
 2 mH
 2 H
 15.9 mH

ANSWER DOWNLOAD EXAMIANS APP